Voltage drop calculator

Sizing the run from your landside breaker panel out to the boat lift control box / motors. Long dock runs eat voltage — under-sized wire makes motors hum, stall, and trip breakers. Target: ≤ 3% drop for motor branch circuits.

Use the motor nameplate FLA × number of motors. Typical Deco 3/4 HP @ 220V draws ~6–8 A per motor running; size for total connected load.

Measure the actual conductor path, not the straight line. Add length for risers, loops, and slack.

Recommended

10 AWG copper

5.59 V drop (2.54%) at 15 A over 150 ft on a 220 V circuit.

GaugeV drop% dropAmpacity
14 AWG14.13 V6.42%20 A
12 AWG8.89 V4.04%25 A
10 AWG5.59 V2.54%35 A
8 AWG3.52 V1.60%50 A
6 AWG2.21 V1.01%65 A
4 AWG1.39 V0.63%85 A
2 AWG0.87 V0.40%115 A
1/0 AWG0.55 V0.25%150 A
2/0 AWG0.44 V0.20%175 A

How to read this

  • Green rows are within the 3% target for motor branch circuits.
  • Yellow rows are 3–5% — workable but motors will start sluggish.
  • Dim rows are either over 5% drop or over the wire's ampacity (!).
  • Formula: VD = 2 × K × I × L ÷ CM (single-phase, K = 12.9 for copper at 75°C). For aluminum, voltages and gauges differ — size up one or two AWG.
  • This is a sizing aid. Final conductor selection must follow your local electrical code (NEC 310 ampacity tables, derating for conduit fill, temperature, and any GFCI / disconnect requirements for marine installs).